Electrical Inspection & Testing
|
Tests Carried Out
|
Continuity of Protective Conductors and Equipotential Bonding
conductors
|
|
If any electrical installation can be
isolated from the supply, it is permissible to disconnect the protective and equipotential
conductors from the main earthing terminal in order to verify their
continuity. The sequence of operation needed for initial testing can be
carried out safely on an existing installation if it is isolated from the
supply. Where an electrical installation cannot be
isolated from the supply, the protective equipotential conductors must NOT be
disconnected as, under fault conditions, the exposed and
extraneous-conductive-parts could be raised to a dangerous level above earth
potential. The 'combined' integrity of the conductors shall be established by
continuity/earth fault loop impedance tests. The former to establish
continuity of conductors and the latter to establish and confirm an
appropriate disconnection time in the event of an earth fault. Polarity
|
|
Test
shall be made to verify that:-
|
|
|
Earth Fault Loop Impedance
Where protective measures are used which
require a knowledge of earth fault loop impedance, the relevant impedance
shall be measured, or determined by an equally effective method. Earth fault loop impedance tests are
carried out at the locations indicated below:-
Where the installation incorporates an
R.C.D., the value of earth fault loop impedance obtained in the test should
be related to the nominal residual operating device. |
Insulation Resistance
Insulation resistance tests should be made
on a dead circuit and any electronic equipment which might be damaged by
application of the test voltage must be disconnected or isolated. The
insulation resistance should be measured between each live conductor and
earth and should not be less than 0.5 megohm. Where practicable the tests are
applied to the whole of the installation with all fuse links in place and all
switches closed. Alternatively, the installation may be tested in parts. |
Operation of Devices for Isolation and Switching
Where means are provided in accordance with
the requirements of the Regulations for isolation and switching, a 10 per
cent sample shall be operated to verify their effectiveness and checked to
ensure adequate and correct labelling. |
Operation of Residual Current Devices (RCD’s)
Where protection is provided by an R.C.D.,
the effective operation of each R.C.D. shall be verified by a test simulating
an appropriate fault condition independent of any test facility incorporated
in the device, followed by operation of the integral test device. The nominal
rated tripping current for protection of a socket-outlet for use with
equipment outdoors or physically installed outside the general installation
equipotential zone must not exceed 30mA (0.03 amps). In certain situations such as high risk
areas, 10mA (0.01 amps) RCD may be appropriate for the particular
installation. |
Operation of Over-Current Circuit-Breakers
Where protection against over current is provided by circuit-breakers, the manual operating mechanism of each circuit breaker will be operated to verify that the device opens and closes satisfactorily. |
|
|
Home
Page OR Product
pages
|
|
|